– For this application use either
insulation with an integral vapour retarder or field apply
a vapour retarder treatment. Apply insulation block board
segments or moulded pipe covering and secure firmly with
mechanical fasteners, wire or banding. Insulation shall be
fitted neatly to all contours without voids. The insulation
shall receive a 12mm dry thickness of hard finish cement
to provide a smoothly contoured surface. Cement to be reinforced
with a layer of reinforcing mesh or reinforcing membrane.
– On resilient type insulation use
reinforcing mesh prior to application of finish cement.
|