7. COMMERCIAL EQUIPMENT

7.1 APPLICATION

B. COLD TANKS AND EQUIPMENT

Specification
Code No.

 
   

1503-C

– For this application use either insulation with an integral vapour retarder or field apply a vapour retarder treatment. Apply insulation block board segments or moulded pipe covering and secure firmly with mechanical fasteners, wire or banding. Insulation shall be fitted neatly to all contours without voids. The insulation shall receive a 12mm dry thickness of hard finish cement to provide a smoothly contoured surface. Cement to be reinforced with a layer of reinforcing mesh or reinforcing membrane.

– On resilient type insulation use reinforcing mesh prior to application of finish cement.

   

Note 1: If air spacing is required behind insulation on breeching, it shall be supplied and installed by others.

Note 2: If chillers are not factory insulated, they shall be insulated in accordance with the manufacturer's specifications.