Annual Conference News and Events Specifications Heat and Frost Denis Formula TIAC Times Members

 

7.0 COMMERCIAL EQUIPMENT

7.2 FINISHES

A. HOT TANKS, BREECHINGS AND EQUIPMENT

Specification
Code No.

 
   

CEF/1

Indoor/Outdoor

   
 

– Over the insulation (hard coat cement not required) apply aluminum jacket secured with sheet metal screws or pop rivets with all joints caulked or flashed to shed water.

   

CEF/2

Indoor

   
 

– Over hard finish cement apply treated fabric jacket using fabric adhesive and finish with one (1) coat of fabric coating. Alternatively, finish with a layer of PVC jacket with all joints and seams sealed.

   

CEF/3

Outdoor

   
 

– Over hard finish cement apply a coat of weather coating (minimum 1 litre per 1.5 m ). While still wet, embed a layer of reinforcing membrane and finish with a coat of weather coating. (minimum 1 litre per 1.5 m ).

   

Note 1: Irregular areas or small heads to be finished with fabric jacket or weather coating to suit application and shell finish.



© TIAC All Rights Reserved – Disclaimer