5. COMMERCIAL PIPING

5.2 FINISHES

Specification
Code No.

 

CPF/1

Indoor

 

 

– The factory applied integral all service jacket shall be neatly applied to receive the treated fabric jacket. Apply a jacket with fabric adhesive.

– Fittings, (valves and strainers if specified) not finished with PVC covers shall be covered with a hard coat cement and finished with treated fitting fabric applied with fabric adhesive.

– Finish fabric with one (1) coat of fabric coating.

 

CPF/2

Indoor (THIS FINISH SHOULD ONLY BE USED WHERE FINISHED APPEARANCE IS NOT A FACTOR)

 

 

– Apply pipe insulation with an integral all-service jacket. Secure jacketing using appropriate fastenings on approximately 100mm centres. Cover longitudinal and circumferential joints with jacket finishing tape neatly applied. Alternately secure jacketing using integral self-sealing lap and self-sealing circumferential joint strips.

– Fittings, (valves and strainers if specified) not finished with PVC covers shall be covered with a hard coat cement and finish with treated fitting fabric applied with fabric adhesive.

 

CPF/3

Indoor/Outdoor (Metal Jacket)

 

 

– Over the pipe insulation apply metal jacketing using necessary fastenings on approximately 150mm centres.

– Over insulated fittings, (valve bodies, valve bonnets, strainers and flanges if specified) apply metal jacket or preformed metal fitting covers to provide a complete jacket system. Secure with necessary fastenings.

 

CPF/4

Indoor/Outdoor (PVC Jacket)

 

 

– Over the pipe insulation apply PVC jacketing using necessary fastenings on approximately 100mm centres. Cover longitudinal and circumferential joints with finishing tape neatly applied.

– Over insulated fittings, valve bodies, valve bonnets, strainers and flanges if specified) apply PVC jacket or preformed PVC fitting covers to provide a complete jacket system. Secure with appropriate fastenings and jacket finishing tape. (See Note 1)

 

CPF/5

Outdoor

 

 

– Over the insulated surfaces apply a coat (minimum 1 litre per 1.5 m ) of weather coating. 2 While still wet, embed a layer of reinforcing membrane and finish with a final coat (minimum 1 liter per 1.5 m ) of weather coating. 2

 

NOTE 1: PVC Jacket and Fittings exposed to outdoor use or fluorescent lighting shall be ultra-violet ray resistant.

 