6. COMMERCIAL DUCTWORK AND PLENUM

Note: The contents of the Section include the application and finishes of duct and plenum insulation under Specification Code Numbers CER, CEF, CIR, CIF, CIU, CRF and CRD. These code numbers are cross referenced in TIAC specification sections 15250 (23 07 00) – Mechanical Insulation and 15270 (23 07 13) – Ductwork Insulation.

6.1 APPLICATION

A. RIGID INSULATION EXTERNAL APPLICATION

Specification
Code No.

 
   

CER/1

Hot Duct and Plenum – (20° to 65°C)

   

 

– Preparation: Fix mechanical fasteners to both horizontal and vertical surfaces at approximately 300 mm centres, each direction.

– Application: Cut insulation without integral vapour retarder to required size and apply to exterior of duct and/or plenum, with horizontal surfaces overlapping vertical surfaces and edges tightly butted together. Secure insulation by impaling on mechanical fasteners. (See Note 1)

   

CER/2

Cold or Dual Temp Duct and Plenum – (Ambient to 65°C)

   
 

– Preparation: Fix mechanical fasteners to both horizontal and vertical surfaces at approximately 300 mm on centres, each direction.

– Application: Cut insulation with integral vapour retarder to required size and apply to exterior of duct and/or plenum with vapour retarder to the warm side with horizontal surfaces overlapping vertical surfaces. Butt edges together tightly. Secure insulation by impaling on mechanical fasteners. Where mechanical fasteners penetrate vapour retarder, and at all corners and joints, apply vapour retarder tape or vapour retarder strips adhered with vapour retarder adhesive. Where raised seams are encountered, secure to the seams an overlapping strip of flexible insulating material with integral vapour retarder to provide a continuous vapour retarder. (See Note 1)

   

CER/3

Outside Air Duct and Plenum – (–40°C to Ambient)

   
 

– As CER/2 above but firstly apply a layer of rigid insulation without vapour retarder before applying layer of rigid insulation with vapour retarder. All joints shall be staggered.

   

Note 1: For external applications of rigid insulation (CER/1 and CER/2) where the use of mechanical fasteners is unsuitable due to space limitations, twine or wire fastenings, insulation adhesive or other suitable method of attachment may be substituted.

Note 2: Except where specifically called for in the Insulation section of the project specifications, where an interior duct liner is used, external insulation shall not be applied.