6. COMMERCIAL DUCTWORK AND PLENUM

6.1 APPLICATION

C. LINER INTERNAL APPLICATION

Specification
Code No.

 
   

CIR/1

Rigid Duct Liner

   

 

– Preparation: Fix mechanical fasteners to both horizontal and vertical surfaces at approximately 300 mm centres each direction.

– Application: Cut insulation material to required size and apply to interior of duct and/or plenum with horizontal surfaces overlapping vertical surfaces and with edges tightly butted together. Insulation shall be applied to the ductwork with a minimum 90% coverage of adhesive and mechanical fasteners. Where mechanical fasteners penetrate factory finish and at all joints, apply a heavy layer of seal coating. On high velocity duct systems 20.32 m/s to 30.48 m/s apply reinforcing membrane over the entire insulation surface. Seal off leading edge of insulation to duct surface with reinforced seal coating.

   

CIF/1

Flexible Duct Liner

   
 

– Preparation: Fix mechanical fasteners to both horizontal and vertical surfaces at approximately 300 mm centres each way.

–Application: Cut insulation material to required size and apply to interior of duct, edges tightly butted together. Insulation shall be applied to the ductwork with a minimum 90% coverage of adhesive and mechanical fasteners. Where mechanical fasteners penetrate factory finish and at all joints, apply a heavy layer of seal coating. On duct systems having a 10.16 m/s to 20.32 m/s velocity, reinforce the joints with seal coating and reinforcing membrane. Seal off leading edge of insulation to duct surface with reinforced seal coating.

   

Note 1: Except where specifically called for in the Insulation section of the project specifications, where an interior duct liner is used, external insulation shall not be applied.

Note 2: Internal insulation shall not be applied to duct work that is below ambient temperature.

 

 