9. FIRESTOPPING,
SMOKE SEALS AND AIR BARRIERS
OVERVIEW: FIRESTOPPING AND SMOKE SEALS
Print
It is critical that the compartmentalization of
a structure – created by the use of fire rated floor, wall and
ceiling assemblies – be maintained in order to reduce the severity
of a fire and the passage of developing smoke and gases to ensure
safety to both life and property.
When penetrations are created
for building services, within a fire rated floor, wall or roof
assembly it becomes critical to seal
these penetrations to a rating equivalent to the fire resistance
rating of the assembly. This design approach will assist in confining
a fire to its origin, thereby giving the building's suppression
system of firefighters a better chance to control it before the
entire structure becomes involved.
The Standards Council of Canada
has adopted criteria for minimum test procedures and performance
standards resulting in acceptable
test methods and standards in Canada. The acceptable test method
in Canada is CAN/ULC-S101-04 ("Standard Methods of Fire Endurance
Tests of Building Construction and Materials"). The acceptable
test standard in Canada is ULC-S115-1995(R2001) "Fire Tests
of Firestop Systems". Both have been included into the National
Building Code. Only testing agencies with Standards Council of
Canada (SCC) accreditation are considered acceptable testing laboratories.
In
Canada, building codes address this issue. National Building Code
of Canada (NBC) – Building Services in Fire Separations and
Fire Rated Assemblies – Fire Stopping of Service Penetrations.
These
subsections specify requirements for the use of "tested" fire
stop materials for sealing building services which penetrate a
fire separation or an assembly required to have a fire resistance
rating.
Service penetration assemblies are assigned a
fire rating when tested in accordance with the Fire Tests of Firestop
Systems,
ULC-S115.
These firestop assemblies are intended for use in openings in fire
resistive wall and/or floor assemblies which are evaluated in accordance
with CAN/ULC-S101.
Under ULC-S115, ratings may be established for
each firestop assembly (F, FT, FH and FTH). An "F" rating
is based upon flame occurrence on the unexposed surface. An "FT" rating
is based upon temperature rise criteria as well as flame occurrence
on the unexposed surface. When a test sample is also subjected
to a hose stream test, "FH" and "FTH" ratings
may be established. An "FH" rating is based upon flame
occurrence on the unexposed surface and acceptable performance
during the hose stream test. An "FTH" rating is based
upon a temperature rise criterion, flame occurrence on the unexposed
surface and acceptable performance during the hose stream test.
The rating of a firestop system applies to its use in the specific
assembly of materials, penetrations, annular spaces and floor or
walls in which it was tested.
Under building code requirements where
piping or ductwork penetrates a fire rated wall or floor assembly,
the joint between the fire
assembly construction and piping or ducts must be sealed with a
fire tested and rated firestopping and smoke seal materials to
prevent the passage of smoke and flame through such joints. Such
firestopping materials shall consist of material that will remain
in place and prevent the passage of flame and smoke when subjected
to the standard fire exposure in CAN/ULC-S101, for a period of
time equal to the protection rating required for the grade of fire
separation.
Under ULC-S115 this is classified as an "F" rating.
The
ULC-S115 definition of temperature rise ("T" rating)
for firestopping materials can be briefly defined as "the
unexposed surfaces of firestop materials or penetrating items shall
not have a measured temperature rise greater than 180°C for
the duration of the hourly time/temperature rating." Firestopping
materials conforming to both flame rating ("F" rating)
and temperature rating ("FT" rating) under ULC-S115 are
classified as having an "FT" rating.
A firestopping system
should not only conform to the relevant flame rating, but equally
important it should have a hose stream test
rating ("H" rating) to prevent passage of gases or water.
In some instances a temperature rise ("T" rating) may
be required to prevent the ignition of highly combustible materials
which may be stored within close proximity to the unexposed side
of the firestopping.
In order to provide a specifier with accurate
and concise specifications which conform to building code requirements,
a suggested single
source specification for firestopping and smoke seals has been
developed for TIAC for incorporation by a specifying authority
in the project specifications.
It is recommended that this single
source specification be incorporated in the project specifications
under a separate section under
Section [07840] [07 84 00]. (Refer to Section 15 of this manual
for a master
specification) |