10. INDUSTRIAL PIPING

10.1 APPLICATION

A. HOT PIPING

Specification
Code No.

 
   

1601-H

Hot Application

   

 

– Piping: Single layer pipe covering without integral jacket shall be held in place with wire for pipe 300 mm diameter or less and banding and wing seals on larger pipe. Double layer staggered joint pipe covering without integral jacket shall have the first layer held in place with wire and the outer layer held in place with banding and wing seals.

– Fittings: Insulate fittings 75mm diameter and less with insulating cement or flexible insulation secured in place with 1.62 mm stainless steel wire and finished with insulating cement to thickness of adjacent pipe covering. Insulate fittings over 75 mm diameter with sections of pipe covering mitred to fit tightly with each mitred section secured in place with a minimum of one loop of 1.62 mm stainless steel wire. All voids and cracks to be filled with insulating cement.

– Valves, Flanges: Insulate valve bodies and flanges with fitted oversized pipe covering, or mitred blocks to thickness of adjacent pipe covering. Expansion joints, steam trap assemblies, unions, slag pocket drain piping & valves, safety relief valves and orifice flanges shall be left uncovered. (See Note 1).

– Insulation Termination Points: Insulation shall be terminated 75 mm from fittings to provide working clearance, and bevel insulation at a 45 degree angle.

 

Note 1: The use of this code number does not include insulation application on valves and flanges. The specifying authority must specify in the project specification, if valves and flanges are to be insulated.