8. SPECIFICATION
CONCEPTS AND EXAMPLES –
COMMERCIAL INSULATION
SPECIFICATION EXAMPLES
8.2 INSULATION – PIPING
Print
Provide and apply piping insulation in accordance
with TIAC Mechanical insulation best practices guide Specification
1501, Piping, as hereinafter specified and/or modified.
1. Scope
– Hot Piping
– Hot Water Heating: A.1 - Mineral Fibre
(low and medium temperature),
25mm thick. (EXAMPLE ONLY)
– Domestic Hot
Water, Including Recirculation: [__________] (No.and type),
[__________] mm thick.
– Steam Piping: [__________] (No. and
type), [__________] mm thick.
– Condensate Piping: [__________] (No.
and type), [__________] mm thick.
– [__________]:[__________] (No. and type),
[__________] mm thick
Spec. Note: State insulation type required
for each scope item, from Group A on Page 1 and 2 of Section
4 - Products.
Insert
insulation thickness required for each scope item.
Add other scope items as
required. If closed cell insulation is selected for
any of the above scope items then, because of different k
factors, state
also the specific trade name of the product required.
2. Scope
– Cold Piping
– Primary Chilled Water Piping: - Mineral
Fibre (low and medium temperature), 25mm thick. (EXAMPLE ONLY)
– Secondary
Chilled Water Piping: [__________] (No. and type), [__________]
mm thick
– Domestic Cold Water Piping: [__________]
(No. and type), [__________] mm thick.
– Interior Rainwater Leaders:
[__________] (No. and type), [__________] mm thick
– [__________]:[__________]
(No. and type), [__________] mm thick.
Spec. Note: State insulation
number and type required for each scope item, from Group A on
Page 1 and 2
of Section
4 - Products.
Insert insulation thickness required for each scope
item. Add other scope items as required. If closed
cell insulation
is
selected for any of the above scope items then,
because of different k
factors,
state also the specific trade name of the product
required.
For induction unit run-outs use TIAC Specification
1501-CA with flexible foamed elastomeric insulation,
______ mm
thick.
Spec Note: Insert thickness required.
3. Scope – Underground Piping
Insulation
Underground piping insulation to be [__________].
Install in accordance with manufacturer's directions.
Spec. Note:
State exact product trade name required, from Group B, Page 2
of Section 4 – Products.
4. Application –
Hot Piping
Apply insulation to hot piping in accordance with
TIAC Specification 1501-H (1501-HA).
Spec Note: Delete 1501-HA if
not applicable.
Include insulation on valve bodies, strainers
and flanges in accordance with TIAC Specification 1501-H.
Spec.
Note: Include in project specification only if required.
5.
Application – Cold Piping
Apply insulation to cold piping in accordance
with TIAC Specification 1501-C (1501-CA)
Spec. Note: Delete 1501-CA
if not applicable.
Include insulation on valve bodies, valve bonnets,
strainers and flanges in accordance with TIAC Specification
1501-C.
Spec. Note: Include in project specification only
if required.
6. Finishes
– Concealed Piping: No further finish
required.
– Exposed Piping: Apply finishes as follows:
Hot
Water Heating: TIAC CPF/1 Indoor (EXAMPLE ONLY)
Domestic Hot
Water: [__________] finish
Steam Piping: [__________] finish
Condensate
Piping: [__________] finish
[__________]: [__________] finish
Primary Chilled Water: TIAC
CPF/1 Indoor (EXAMPLE ONLY)
Secondary Chilled Water: [__________]
finish
Domestic Cold Water: [__________] finish
Interior
Rainwater: [__________] finish
[__________]: [__________]
finish
Spec Note: Select finish from TIAC CPF/1 to CPF/5
as listed on Page CP-5 and CP-6. Include
finish for each scope item
as required.
Add other scope items as required. |