8. SPECIFICATION
CONCEPTS AND EXAMPLES –
COMMERCIAL INSULATION
SPECIFICATION EXAMPLES
8.3 INSULATION – DUCTWORK AND PLENUM
Print
Provide and apply insulation to ductwork and plenums
in accordance with TIAC Mechanical insulation best practices guide
Specification 1502, Ductwork and Plenum, as hereinafter specified
and/or modified.
1. Scope – Externally Applied
– Outside Air Ductwork
(Intake to Mixing Plenum): [__________] mm thick, – rigid
insulation (with vapour retarder)
– Sheet Metal Air Conditioning Supply
Air Ductwork: [__________] mm thick,
[__________] mm thick, rigid
insulation (with vapour retarder) where exposed.
[__________]
mm thick, – flexible insulation (with vapour retarder) where
concealed.
– [__________]
Spec Note: Insert required thickness. Add other
scope items as required.
2. Scope – Internally Applied
– Rigid Duct Liner:
Mixed air plenum [__________] mm thick.
– Rigid Duct Liner: Filter/Coil
plenum [__________] mm thick
– Rigid Duct Liner: Fan plenum [__________]
mm thick.
– [__________]
Spec. Note: Insert required thickness for each
scope item. Add other scope items as required.
Acoustic lining, where indicated
or denoted as such on the drawings, use xx mm thick flexible
duct liner.
Spec Note:
Delete if not applicable. Insert thickness required.
3.
Application – Rigid External (Duct and Plenum)
– Hot: Apply insulation
in accordance with TIAC Specification CER/1.
– Cold: Apply insulation
in accordance with TIAC Specification CER/2.
Spec Note: Delete item not applicable.
4. Application – flexible
external (Duct and Plenum)
– Hot: Apply insulation in accordance
with TIAC Specification CEF/1.
– Cold: Apply insulation in accordance
with TIAC Specification CEF/2.
Spec Note: Delete item not applicable.
5. Application – Liner Internal
(Duct)
– Rigid: Apply insulation in accordance
with TIAC Specification CIR/1.
– Flexible: Apply insulation in accordance
with TIAC Specification CIF/1.
Spec Note: Delete items not applicable.
6. Finishes – Rectangular
Ducts
– Concealed Ducts: No further finish required.
– Exposed Ducts: Apply TIAC CRF/1 – Indoor
(CRF/2 -– Indoor) (CRF/3 – Outdoor) (CRF/4 – Outdoor)
Spec Note: Select
finish required. Delete finishes not applicable. Include finish
for additional scope
items
as required.
7. Finishes – Round Ducts
– Concealed Ducts:
No further finish required.
– Exposed Ducts: Apply TIAC CRD/1
– Indoor (CRD/2 – Indoor) (CRD/3 – Indoor) (CRD/4 – Outdoor)
(CRD/5 – Outdoor ).
Spec. Note: Select finish required. Delete finishes
not applicable. Include finish for additional
scope items
as required. |